1 inch pipe outside diameter

1" PVC and steel pipe are 1.315" (33.4 mm) across the outside. 1" copper, PEX and CTS CPVC are 1.125", which is 1-1/8" (28.6 mm).

1 inch pipe sizes by type

1" pipe and tube: outside diameter, inside diameter and wall
PipeOutside (OD)Inside (ID)Wall
PVC Schedule 401.315" (33.4 mm)n/a0.133"
PVC Schedule 801.315" (33.4 mm)n/a0.179"
CPVC Schedule 80 (Charlotte Corzan)1.315" (33.4 mm)n/a0.179"
Steel Schedule 40, black or galvanized1.315" (33.4 mm)1.049"0.133"
Steel Schedule 801.315" (33.4 mm)0.957"0.179"
Copper Type K1.125" (28.6 mm)0.995"0.065"
Copper Type L1.125" (28.6 mm)1.025"0.050"
Copper Type M1.125" (28.6 mm)1.055"0.035"
PEX (Uponor AquaPEX)1.125" (28.6 mm)0.862"n/a
CTS CPVC (FlowGuard Gold)1.125" (28.6 mm)n/a0.102"

PVC, ABS and CPVC: Charlotte Pipe’s average OD and minimum wall; its Corzan Schedule 80 CPVC is iron pipe size. Copper: the Copper Development Association’s nominal sizes. Steel: Wheatland Tube’s table. PEX: Uponor AquaPEX, whose table gives OD and ID. A cell marked n/a isn’t in the maker’s table.

PVC and steel follow iron pipe size, copper, PEX and CTS CPVC copper tube size. At 1" the iron pipe size is 0.19" wider than copper tube size. Schedule 80 and Type K keep the same outside as the thinner pipe and tube of their kind, with a smaller inside.

What fits a 1 inch pipe

Measuring your pipe

Measure across the end at its widest point. 1" copper (1.125") is only 0.075" wider than 3/4" PVC (1.050"), so work out the kind of pipe first: what pipe do I have? For the coin check on smaller pipe, see how to tell pipe size.

Common questions

What is the inside diameter of 1 inch PEX?

Uponor AquaPEX is 0.862" inside and 1.125" outside. Other makers' PEX has the same outside, as PEX is copper tube size; check the maker's sheet for its inside.

What is the inside diameter of 1 inch Schedule 40 steel pipe?

1.049" in Wheatland Tube's table, with a 0.133" wall. Its 1" Schedule 80 is 0.957" inside with a 0.179" wall.

How thick is 1 inch copper pipe?

In the Copper Development Association's tables, Type K has a 0.065" wall (0.995" inside), Type L 0.050" (1.025") and Type M 0.035" (1.055").

Available on Amazon

As an Amazon Associate, What Adapter For earns from qualifying purchases.

Where we get our information from

The sizes come from the pipe makers’ own tables (Charlotte Pipe, Wheatland Tube, Uponor) and the Copper Development Association’s tube tables; the thread from the National Bureau of Standards tables and the fitting size from SharkBite’s installation guide. Checked against published data from Uponor, SharkBite, National Bureau of Standards, Charlotte Pipe and Copper Development Association (plus 1 more).

See all 9 sources
  • National Bureau of Standards, Handbook H28 (1957) Part II: Table VII.2 (American Standard taper pipe threads, NPT) and Tables X.1–X.3 (hose coupling threads, NH)
  • Uponor, Plumbing Design Assistance Manual (PEX is copper tube size)
  • SharkBite (Reliance Worldwide), SharkBite Installation Guide (2020): pipe insertion depth table, integral PEX stiffener
  • SharkBite (Reliance Worldwide), SharkBite PEX Installation Guide (2021): fits copper, CTS CPVC and PEX in any combination
  • Uponor, PEX Piping Systems Installation Guide, seventh edition (2025): ProPEX expansion fittings, pipe colors, copper and threaded adapters, no soldering within 18" of PEX
  • Charlotte Pipe, Plastics Technical Manual (2026), product data: average outside diameter and minimum wall of PVC Schedule 40 and 80, PVC DWV, PVC and ABS foam core, 4" sewer and drain pipe, and CTS CPVC
  • Copper Development Association, The Copper Tube Handbook (2026), Tables 14.2a-d: outside diameter, inside diameter and wall of Type K, L, M and DWV tube; outside diameter 1/8" over the standard size
  • Uponor, Uponor AquaPEX white straight lengths submittal (2026): inner and outer diameter, 1/2" to 3"
  • Wheatland Tube, Standard Pipe (SureThread and ERW) brochure: ASTM A53 Schedule 40 and 80 outside diameter, inside diameter and wall, black and galvanized, ASME B36.10M

General guidance from manufacturer and standards data. Parts vary by brand, so check the size printed on the package against what you measured. For gas lines or anything inside a wall, use a licensed plumber.