What size is a sump pump discharge pipe?

Zoeller’s Model 53, Liberty’s 250-Series, Wayne’s CDU800 and Little Giant’s 6 Series all have a 1-1/2" threaded discharge. Run the discharge pipe at least that size.

Discharge size by pump

Sump pump discharge sizes, from the makers’ own pages and manuals
PumpDischargeThe maker on the pipe
Zoeller Model 531-1/2" NPTNo discharge pipe smaller than the pump discharge, with a check valve and a union in the line
Liberty 250-Series1-1/2" threadedNot below the size on the pump, and Schedule 40 PVC pressure pipe recommended
Wayne CDU8001-1/2" NPTRigid PVC required, and no flex hose in a permanent installation
Little Giant 6 Series1-1/2" female pipe thread; some models come with a 1-1/4" FNPT reducing bushingNo piping smaller than the pump discharge, and pipe joint compound at every connection

Other models from these makers can differ. The size is on the pump’s spec sheet or in its manual.

1-1/4 or 1-1/2 inch pipe?

Some of Little Giant’s 6 Series pumps come with a 1-1/4" reducing bushing, so the pump can take 1-1/4" pipe. Its manual still says not to use piping smaller than the pump discharge, and the IPC (section 1113.1.4) asks for pipe and fittings the same size as, or larger than, the pump’s discharge tapping. On a 1-1/2" discharge, 1-1/2" pipe meets both. Liberty adds that a long run may need a larger pipe to cut friction loss. Local code decides, so check with your building department.

For what 1-1/2" pipe measures across, see 1-1/2" pipe OD.

What goes in the discharge line

The relief hole

With a check valve in the line, Zoeller, Liberty and Little Giant call for a small hole in the discharge pipe between the pump and the check valve, to let trapped air out. The size differs by maker. Zoeller says about 3/16", Liberty 1/8", and Little Giant 1/8" or 3/16". Wayne’s CDU800 has a top suction design that, in Wayne’s words, needs no weep holes. Zoeller puts the hole below the basin cover, and a small stream from it while the pump runs is normal. Follow your own pump’s manual.

Where the water goes

Where a sump pump may discharge is set by local code. Little Giant lists the house drainage system, a dry well, a splash block or a storm drain, depending on local plumbing codes. Wayne’s manual has the water carried at least 3 feet from the foundation, with the pipe sloping down and away where it can freeze. Ask your building department before you tie into any drain or sewer.

Unplug the pump before you touch it or its discharge pipe. If the floor around the pit is flooded, stay out of the water and have your electric company or a licensed electrician shut off the power first. Electrical work for a sump pump, such as its outlet or circuit, is a job for a licensed electrician.

Common questions

Can I use a garden hose as a sump pump discharge?

Not for a permanent setup in Wayne's manual, which requires rigid PVC and no flex hose. Little Giant includes a 3/4 inch garden hose adapter with some 6 Series models.

What size check valve does a sump pump need?

One that matches the discharge pipe. Zoeller's 30-0181 fits 1-1/4 or 1-1/2 inch Schedule 40 PVC.

How tight should the pipe be in the pump?

Liberty says to hand-tighten the discharge pipe into its 250-Series pump, since overtightening may crack the pump housing. Little Giant calls for pipe joint compound at all connections.

Available on Amazon

As an Amazon Associate, What Adapter For earns from qualifying purchases.

Where we get our information from

The discharge sizes and the parts in the line come from the pump makers’ own product pages and installation manuals, and the pipe size rule from the IPC as adopted in South Carolina. Checked against published data from Zoeller, Liberty Pumps, Wayne, Little Giant and International Code Council.

See all 5 sources
  • Zoeller, Model 53 sump pump product page (1-1/2" NPT discharge), Installation Instructions FM2676 (check valve, union, discharge pipe no smaller than the pump discharge, 3/16" vent hole, licensed electrician) and check valve pages (30-0181, 1-1/4" or 1-1/2" slip x slip)
  • Liberty Pumps, 250-Series product page and Installation Manual 7035000R: 1-1/2" threaded discharge, Schedule 40 PVC, hand-tighten, union and check valve, 1/8" anti-airlock hole, larger pipe on long runs, certified electrician
  • Wayne, CDU800 sump pump product page and Operating Instructions and Parts Manual 600002W: 1-1/2" NPT discharge, top suction with no weep holes, rigid PVC and no flex hose, check valve required, gate or ball valve if code requires, 3 ft from the foundation
  • Little Giant (Franklin Electric), 6-Series sump pump product page and Owner's Manual 993865: 1-1/2" female pipe thread discharge, a 1-1/4" FNPT reducing bushing and a garden hose adapter on some models, no piping smaller than the discharge, horizontal check valve, 1/8" or 3/16" relief hole, discharge by local code
  • International Plumbing Code 2021, sections 1113.1.3 and 1113.1.4: sump pump electrical outlets to NFPA 70; discharge pipe the same size as or larger than the pump discharge, gate valve and full-flow check valve (as adopted in South Carolina)

General guidance from manufacturer and standards data. Parts vary by brand, so check the size printed on the package against what you measured. For gas lines or anything inside a wall, use a licensed plumber.